XR500 Series Canadian Programming Guide Digital Monitoring Products
27
SYSTEM OPTIONS
System Options
9.1
SYSTEM OPTIONS
System Options
Thissectionallowsyoutoselectsystem-wideparameters.
9.2
SYSTEM: AREA
System
This option allows you to program how the areas operate for arming and disarming.
The options you can choose are listed below:
AREA A/P H/A GST
AREA - All 32 areas can be programmed and operated independently.
ALL/PERIMETER - Area 1 is the Perimeter and Area 2 is the Interior.
HOME/SLEEP/AWAY - Area 1 is the Perimeter, Area 2 is the Interior, and Area 3 is the
Bedrooms.WiththeHOME/SLEEP/AWAYoption,theusercan:
1. Select HOME to arm just the perimeter.
2.SelectSLEEPtoarmtheperimeterandinterior(nonbedroomareas).
3. Select AWAY to arm all three areas.
Note:AHome/Sleep/Awaysystemcanbeconguredtouseallthreeareasor
only use the Home and Away areas.
HOME/SLEEP/AWAY WITH GUEST- This allows the alarm system to be divided into a
mainhouseHOME/SLEEP/AWAYsystemandtwootherguesthousesthatalsoareset
upasHOME/SLEEP/AWAYsystems.
Areas 1, 2, and 3 are the Perimeter, Interior, and Bedrooms for the Main house
system.Areas4,5,and6arethePerimeter,Interior,andBedroomsfortheGuest
1housesystem.Areas7,8,and9arethePerimeter,Interior,andBedroomsfor
theGuest2housesystem.Theseareasareautomaticallyassignedpersystemand
cannot be changed. See Display Areas in Device Setup to assign keypads to a system.
Zones are assigned to a system by assigning the system’s area numbers to the zone in
Zone Information programming.
WheneitherAll/PerimeterorHome/Sleep/Awayisselected,theareanamesare
automaticallyassignedandcannotbemodied.
Note:Areas3-32inanAll/Perimetersystem,areas4-32inaHome/Sleep/Away
system,andareas10-32inaHome/Sleep/AwaywithGuestsystemarenotavailable
for use and are initialized.
9.3
INST ARM NO YES
Instant Arming
When YES is selected, the arming keypad displays INSTANT for selection during the exit
countdown delay when arming fewer than all areas of the system. At the time instant
arming is selected, any entry and exit delays programmed for the areas being armed
are ignored. The entry delay for previously armed areas is not affected by instant
arming. When NO is selected, INSTANT does not display during arming. Default is NO
foranAreaSystem,andYESforanAll/PerimeterorHome/Sleep/Awaysystem.
9.4
CLS WAIT NO YES
Closing Wait
When YES is selected, the keypad displays ONE MOMENT... while waiting for
anacknowledgementfromthereceiverbeforearmingtheselectedarea(s)and
performingaBellTest(ifselected).ExitdelaysbeginaftertheClosingWait.
Opening/ClosingreportsmustbeYEStoenableClosingWait.
9.5
ENTRY DLY 2: 60
ENTRY DLY 3: 90
ENTRY DLY 1: 30
ENTRY DLY 4: 120
Entry Delay 1
Enter the Entry Delay time for all Exit type zones programmed to use Entry Delay 1.
When an armed Exit type zone is faulted, the keypad prewarn tone begins sounding.
AllkeypadsprogrammedtoprewarnforthatzonedisplayENTERCODE:-andthe
nameofthezonecausingtheentrydelay.Whentherstdigitofacodeisentered,
the prewarn tone stops at that keypad. If an invalid code is entered, the prewarn
tone begins sounding again. The area must be disarmed before the delay expires
or an alarm report is sent to the receiver and an alarm sounds. All zones in that
area are delayed along with the Exit zone. Entry Delay times can be from 30 to 250
seconds. Repeat the above for each entry delay being used in the system.
Note:SpecicExitErroroperationisbasedontheEntryDelayused(1-4)withanEX
type zone. See Exit Delay.
Comentarios a estos manuales