Dmp-electronics DMP Command Processor Panel XR500 Manual de usuario Pagina 80

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 85
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 79
XR500 Series Canadian Programming Guide Digital Monitoring Products
71
APPENDIX
23.12 ZoneTypeSpecications
TheXR500SeriesCanadianpanelcontainsmultipledefaultzonetypesforuseinconguringthesystem.
These zone types provide the most commonly selected functions for their applications. All zone types
can be customized by changing the variable options listed below. The Keypad Bus Zone Information table
belowreectsthezonetypesforKeypadBusZones.TheXR500SeriesLX-BusZoneInformationtableon
thenextpagereectsthezonetypesforLX-BusZones.
Keypad Bus Zone
Information
Type Area Fire
Bell
Disarmed
Open
Disarmed
Short
Armed
Open
Armed
Short
Swinger
Prewarn
Entry Delay
Retard Delay
Presignal
Fast Response
Cross Zone
Priority
Follow Area
Real-Time Rprts
Door Number
Style
Assign Disarm condition of
NT, DY, EX, A1, and A2 only
Assign Prewarn and Entry
Delay for EX only
Assign Retard and Presignal
for FI, SV, A1, and A2 only
Zone Type Defaults
--
DY
FI
EM
A1
FV
NT
EX
PN
SV
A2
AR
INT
PERIM
BDRM
or
1
to
32
Output *
Message
Output *
Action
Message
Output *
Action
Message
Output *
Action
Message
Output *
Action
A
T
L
-
D
S
C
S
P
M
F
A
T
L
-
D
S
C
S
P
M
F
A
T
L
-
D
S
C
S
P
M
F
A
T
L
-
D
S
C
S
P
M
F
N
or
Y
1
to
16
1
or
4
N
or
Y
1
to
16
N
or
Y
N
or
Y
N
or
Y
0
to
16
N
or
Y
0
to
16
TGL
ARM
DIS
STEP
MNT
Night NT - 0 S - 0 S A 0 S A 0 S Y N N N 0 N 0
Day DY T 0 S T 0 S A 0 S A 0 S Y N N N 0 N 0
Exit EX - 0 S - 0 S A 0 S A 0 S Y
1-16
1 N N N N 0
Fire FI 0 T 0 S A 0 S N N + N N N
Panic PN T 0 S A 0 S N N N N
Emergency EM T 0 S A 0 S N N N N
Supervisory SV 0 T 0 S A 0 S N N + N N N
Auxiliary 1 A1 T 0 S A 0 S T 0 S A 0 S N N + N N N 0 N 0
Auxiliary 2 A2 T 0 S A 0 S T 0 S A 0 S N N + N N N 0 N 0
Fire Verify FV 0 T 0 S A 0 S N N N
Arming AR TGL
*OutputOptions:1to6,450to474,480to499,500to999,D1toD16,G1toG20. + =SetretardtoYESbeforeselectingpresignal. =Zonefunctionsnotavailable.
23.12.1
Keypad Bus Zone Type Defaults
These are complete spellings of the abbreviations used for the zone types, such as Night and Exit.
Type -Thesearetheabbreviationsusedforthezonetypes,suchasNTandEX.
Area-ForanAreaorHome/Sleep/AwaywithGuestsystemthisis1to32.ForanAll/PerimeterorHome/
Sleep/Awaysystem,thisistheInterior,Bedroom,orPerimeter.SelecttheareaforNT,DY,EX,A1,A2,and
AR types.
Fire Bell Out -OnlyavailableforFI,FV,andSVzones.Useanyoutputzonenumberlisted.
Message -A=alarmreport,T=troublereport,L=local,noreport,(dash)=noreport,D=doorpropped
(WhenSVzoneisconnectedto303Silence/ResetSwitch),S=sensorreset/alarmsilence,
C=earlymorningambushcancel.
Output -Theseare1to6on-boardand500to999off-boardrelayoutputs,450to474and480to499
wirelessoutputs,D1toD16,andG1toG20.
Action -Thisselectstheactionoftheoutput:S=steady,P=pulse,M=momentary,andF=follow
Swinger -Thezonecanbeautomaticallybypassedafteraprogrammednumberoftrips.
Prewarn -Thisselectsthekeypadaddressthatsoundstheentryprewarnforthiszone.
Entry Delay-Thisistheentrydelaytimerselectedasthedefaultforthiszone.
Retard Delay-Providesaprogrammedretardtimebeforeanalarminitiatesfromashortedzone.When
used on an arming zone, the retard delay occurs when the zone is shorted before the armed state has
changed. If the arming zone has Maintain as the Style, the retard delay also occurs when the zone returns
to a normal state.
Presignal -Providesakeypadtoneforzonesinretarddelay.RetardmustbeYESbeforePresignalcanbe
selected.
Fast Response-Providesa167mszoneresponseinsteadofthenormal500msresponse.
Cross Zone-Providescrosszoningwithanyofthe574zones.
Priority -Requiresthiszonetobeinanormalconditionbeforetheareacanbearmed.
Style - The abbreviations for arming zone style:
TGL=Toggle,ARM=Armonly,DIS=Disarmonly,STEP=Wirelessarming,MNT=Maintain