Dmp-electronics DMP Command Processor Panel XR500 Manual de usuario Pagina 69

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 85
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 68
Digital Monitoring Products XR500 Series Canadian Programming Guide
60
ZONE INFORMATION
19.24
CRS ZONE NO YES
Cross Zone
Select YES to enable cross zoning for this zone. Cross zoning requires one or more armed
zones to fault within a programmed time before an alarm report is sent to the receiver.
Whentherstcrosszonedzonetrips,thecrosszonetimespeciedinSystem
Optionsbeginstocountdown.Whenasecondcrosszonedzonetripsortherst
zone trips a second time before the end of the count down, the bell action assigned
to the zone activates and the panel sends an alarm report for both zones.
If no other cross zoned zone trips before the cross zone time expires, the panel
sends only a zone fault report to the receiver.
Cross zoning is not compatible with all zone types: You can not enable cross zoning
for Fire verify zones or for any Fire zones that have Retard Delay enabled.
19.25
PRIORITY NO YES
Priority
Select YES to provide additional protection for the premises by requiring this zone to
be in a normal condition before its assigned area can be armed.
19.26 Fire Panel Slave Input
ThisoptionisavailableonFireZones(FI)onlyandallowsarezonetheabilityto
provideslavecommunicationoperationforaseparaterealarmcontrolpanel.If
YES,thiszonewilltransmitarestoralimmediatelywhenrestoredbytherepanel
being monitored. A sensor reset is not required to generate the restoral message.
IfNO,thiszonewilloperateasastandardretypezoneandasensorresetis
required before the zone will return to normal. Default is NO.
19.27 Area Follower
Allows Night, Day, Aux 1, or Aux 2 burglary zones to be delayed by following any exit
orentrydelaythatiscurrentlyrunningintheareathatisspecied.Defaultis0.
19.28 Zone Real-Time Status
SelectingYESallowsReal-TimeStatusreports,suchasDoorOpenorClosedwith
zonenumber,tobesentusingPCLogreporting.SelectingNOdisablesReal-Time
Status for this zone. Default is NO.
19.28.1 Door Number
IfZONEREAL-TIMESTATUSisselectedasYES,enteradoornumber(keypadbus
address)of1-16.Whenadoornumberisselected,thedoornumberisincluded
inthestatusreportinsteadofthezonenumber.Enter0(zero)todisablethis
featureandreportthezonenumber.Defaultis0(nodoor).
19.29
ZONE AUDIT DAYS:
Zone Audit Days
Enterthenumberofdays(0to365)allowedtoelapsewithoutthezonebeingtripped
beforeafaultmessageissent.Themessageissenttothereceiver(s)programmed
toreceiveSupervisory/TroubleReportsat10:00amfollowingtheexpirationofthe
timer. Each time the zone is tripped, the Zone Audit Days timer restarts and begins
to countdown the number of days programmed. After the countdown expires, a fault
message is sent and the Zone Audit Days timer restarts and begins to countdown the
numberofdaysprogrammed.Availableforallzonetypesexceptreandreverify.
Enter0(zero)todisablethisfunction.Defaultis0(zero).
19.30 Report with Account Number for Area
Thisoptionisonlyavailablefor24-hourzonetypes(Fire,FireVerify,Panic,
Emergency,orSupervisory).
Entertheareanumber(1-32)toassignasa24-hourzonetype.Thisoption
sends
the account number of the programmed area with messages. If the entered area
number does not exist or is not valid, the account number programmed in the
Communicationsectionissent.Select0(zero)tohavethereportsentwiththe
account number programmed in Communication. Default is 0
FOLLOW AREA: 0
ZONE REAL-TIME
STATUS
NO YES
FIRE PANEL SLAVE
INPUT: NO YES
DOOR NUMBER: 0
0
REPORT WITH ACCT
NO. FOR AREA: 0
SET LOCKOUT CODE
Vista de pagina 68
1 2 ... 64 65 66 67 68 69 70 71 72 73 74 ... 84 85

Comentarios a estos manuales

Sin comentarios