XR500 Series Canadian Programming Guide Digital Monitoring Products
53
ZONE INFORMATION
consecutive zone numbers. Default is Contact 1.
Forexample,useserialnumber08345678toprogramContact1forZone561,
Contact2forZone562,Contact3forzone563,andContact4forzone564.
A tamper on the 1114 is transmitted as the zone number assigned to Contact 1.
ALREADY IN USE
ZONE NUMBER: XXX
This message displays when the Contact is already programmed for another
zone. The programmed zone number displays.
ZONE INFORMATION
NORM OPN NO YES
This option only displays when EXT is selected as the Contact type. For external
devices connected to the 1101 or 1103 terminal block, select NO to use normally
closed(N/C)contacts.SelectYEStousenormallyopen(N/O)contacts.Default
is NO.
19.10.3
TRANSMITTER
SUPRVSN TIME: 240
Supervision Time
Press any top row key to select the supervision time required for the wireless
zone. Press COMMAND to accept the default time. Default is 240 minutes.
Note:RefertotheWirelessCheck-inandSupervisionTimeDenitionssection
of the Appendix for supervision information.
SELECT MINUTES:
0 3 60 240
Press the Select key under the required number of minutes. The transmitter
must check in at least once during this time or a missing condition is indicated
for that zone. 1100 Series transmitters automatically checkin based on the
supervision time selected for the wireless zone, no additional programming
is needed. If two zones share the same transmitter, the last programmed
supervisiontimeisstoredasthesupervisiontimeforbothzones.Zero(0)
indicates an unsupervised transmitter.
The3minutesupervisiontimeisonlyavailableforzonetypesofFire(FI),Fire
Verify(FV),andSupervisory(SV).
Note: When the panel is reset or a receiver is installed or powered down and
powered up, the supervision timer restarts for all wireless zones.
19.10.4
LED OPERATION
NO YES
LED Operation
SelectYEStoturnonan1142Hold-uptransmitterLEDduringPanicor
Emergencyoperation.SelectNOtoturntheLEDoffduringPanicorEmergency
operation.TheLEDalwaysoperateswhenthetransmittercaseisopenandthe
tamper is faulted. Default is YES.
19.10.5
DISARM DISABLE
NO YES
Disarm/Disable
SelectYEStodisablethezonetrippedmessage(short)tothe1100XSeries
Receiverfromthe1126PIRtransmitterduringthedisarmedperiod.When
disabled,the1126onlysendssupervision,tamperandlowbatterymessages
during the disarmed period to extend transmitter battery life. Select NO to
always send zone tripped messages in addition to supervision, tamper and low
battery. Default is YES.
19.10.6
WIRELESS PIR
PULSE COUNT: 4
PIR Pulse Count
Selectthenumberofinfraredpulses(2or4)the1126PIRshouldsensebefore
sending a short message to the 1100X Series Receiver. Default is 4.
19.10.7
WIRELESS PIR
SENSITIVITY:LOW
PIR Sensitivity
Selectthesensitivitysettingforthe1126PIR.SelectingLOWsetsthe1126to
operateat75%sensitivityforinstallationsinharshenvironments.Selecting
HIGHsetsthePIRtomaximumsensitivity.DefaultisLOW.
19.10.8
NEXT ZONE NO YES
Next Zone
SelectYEStoreturntotheZONENO:-prompttoprogramanewzone.Select
NO to display the Alarm Action option.